Navien · General troubleshooting

Replacing the chlorine tablet pouch holder assembly

WEC

What is going on

Swap the pouch holder in the sediment pre-filter housing. Use the pouch holder that matches the supply pipe size.

Check in this order

  1. Close the inlet and outlet valves.
  2. Open the bypass valve.
  3. Release pressure from the filter by pressing the red pressure release button on the sediment pre-filter housing cover. If there is no release button, close the bypass valve, open the outlet valve and the nearest cold water faucet, then close the outlet valve, open the bypass valve and close the faucet once pressure is released. Do not drain all the plumbing water.
  4. Remove the sediment pre-filter housing with the filter housing wrench.
  5. Check that a chlorine tablet is in the tablet pouch of the kit. If not, contact Technical Support.
  6. Check the supply pipe size (1 in. or 3/4 in.) and select the matching pouch holder.
  7. Insert the pouch holder assembly into the sediment pre-filter housing cover, aligned with the IN marking on the water inlet.
  8. Center the cartridge in the filter housing and tighten with the filter housing wrench.
  9. Close the bypass valve and open the inlet and outlet valves.

Applies to: WEC600 (sediment pre-filter housing)

More general guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien WEC service manual, p. 117-118. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.