Navien · General troubleshooting

Replacing the check valve

WEC

What is going on

Remove the back cover and replace the check valve in the outlet water pipe assembly. Protect the O-rings on the adapters.

Check in this order

  1. Turn off the feedwater supply.
  2. Disconnect power to the WEC.
  3. Remove the back cover (see page 82).
  4. Remove the 4 L-clips from the check valve and Y-adapter, then lift the check valve up and off.
  5. Insert the O-rings into both adapters and fit the new check valve onto the manifold and Y-adapter.
  6. Fit the 4 L-clips onto the check valve and Y-adapter.
  7. Reinstall the back cover and secure it with 11 screws.

Applies to: WEC600

More general guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien WEC service manual, pp. 91-92. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.