Navien · General troubleshooting
Replacing the bypass valve
What is going on
Remove the back cover, loosen the check valve, then remove and replace the bypass valve. Protect the O-rings on the adapters.
Check in this order
- Turn off the feedwater supply.
- Disconnect power to the WEC.
- Remove the back cover (see page 82).
- Remove the 4 L-clips from the Y-adapter and manifold to loosen the check valve.
- Remove the 2 L-clips and the connector from the bypass valve, and take the bypass valve out while holding the check valve in place.
- Insert the O-rings into the adapters, fit the bypass valve onto the T-adapter and manifold, then reinstall the 2 L-clips and connect the harness connector to the bypass valve.
- Reinstall the back cover and secure it with 11 screws.
Applies to: WEC600
More general guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien WEC service manual, p. 93. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.