Replace the TDS sensor for the product/regeneration water pipe

WEC Series

What is going on

The CIP tank must come out to reach this sensor. Be careful with CIP solution: a spill can corrode the unit, and if it contacts skin or eyes, flush with running water right away.

Check in this order

  1. Turn off the feedwater supply.
  2. Disconnect the power supply from the WEC.
  3. Remove the 2 screws on each side of the front cover and set the cover aside.
  4. Remove the 4 screws from the CIP tank assembly and pull the tank out of the WEC. Avoid spilling the solution.
  5. Place the CIP tank on a flat, clear surface.
  6. From the back of the CIP tank, disconnect the water level sensor connector and CIP dosing pump connector from the harness.
  7. Disconnect the TDS sensor connector from the harness.
  8. Loosen the sensor nut with a wrench and remove the TDS sensor assembly from the Y-adapter.
  9. Install the new TDS sensor assembly on the Y-adapter and tighten the nut with a wrench.
  10. Connect the TDS sensor connector to the harness.
  11. From the back of the CIP tank, reconnect the water level sensor and CIP dosing pump connectors to the harness.
  12. Install the CIP tank in the WEC and secure with 4 screws.
  13. Align the front cover with the WEC and secure each side with 2 screws.

Applies to: WEC600

More general guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien WEC service manual, p. 97-98. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.