Navien · General troubleshooting

Replace the sediment pre-filter cartridge

WEC Series

What is going on

Procedure for changing the sediment pre-filter cartridge. Replace about every 6 months, or sooner if flow or pressure drops or the REPLACE FILTER icon lights.

Likely causes

  • Flow or pressure loss at fixtures may mean the cartridge needs changing before the indicator comes on.
  • Water quality can shorten cartridge life.

Check in this order

  1. Unplug the WEC power cord (power off). An error will block filter replacement if power is still on.
  2. Close the inlet and outlet valves.
  3. Open the bypass valve.
  4. Press the red pressure release button on the sediment pre-filter housing cover. If there is no button, close bypass, open outlet and a nearby cold faucet, then close outlet, open bypass and close the faucet. Do not drain the whole plumbing.
  5. Unscrew the housing with the filter housing wrench.
  6. Remove and discard the used cartridge.
  7. Clean inside the housing.
  8. Install the new cartridge with the top gaskets in place and centered, then tighten with the wrench.
  9. Close bypass and service valves, then open inlet and outlet valves.
  10. Press the red pressure release button to purge air from the housing.
  11. Plug the power cord in. The WEC starts Auto Flushing and then goes to standby.
  12. Reset the sediment pre-filter use period press and hold Back, OK and Next for 3 seconds (see 3.7, p. 36).
  13. Keep the inlet and outlet plugs in place until installation. Do not leave internals exposed to air for more than 4 hours.

Applies to: WEC Series sediment pre-filter

More general guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien WEC Series Service Manual, p. 42-43. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.