Replace the regeneration solenoid valve
What is going on
Procedure for the regeneration solenoid valve and its flow switch. Several steps appear in a mixed order on the extracted pages, so check each step against the physical parts as you go.
Check in this order
- Turn off the feedwater supply.
- Disconnect the power supply from the WEC.
- Remove the back cover from the WEC.
- Disconnect the flow switch connector from the harness.
- Remove the L-clip from the drain adapter and disconnect the connector from the regeneration solenoid valve.
- Remove the screw holding the flow switch assembly to the case and take the flow switch assembly out.
- Remove the 2 screws from the valve guide.
- Remove the L-clip from the V-adapter and take the regeneration solenoid valve assembly out of the unit.
- Remove the 2 screws from the valve guide and take the regeneration solenoid valve off the assembly.
- Fasten the valve guide to the new regeneration solenoid valve with 2 screws.
- Install the regeneration solenoid valve assembly and fit the L-clip on the V-adapter.
- Install the 2 screws into the valve guide.
- Install the flow switch assembly and secure it to the case with its screw.
- Install the L-clip on the drain adapter and connect the harness connector to the regeneration solenoid valve.
- Connect the flow switch connector to the harness.
- Place the back cover on the WEC and secure with 11 screws.
Applies to: WEC600
More general guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien WEC service manual, p. 101-103. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.