Replace the product water solenoid valve
What is going on
Accessed from the back of the unit after the back cover is removed. Keep track of the O-rings on the adapters so they are not lost or damaged.
Check in this order
- Turn off the feedwater supply.
- Disconnect the power supply from the WEC.
- Remove the back cover from the WEC.
- Remove the 2 L-clips from the Y-adapter and manifold, then lift the check valve out upward.
- From the product/regeneration water pipe assembly, remove the 2 L-clips and connectors.
- Pull the product water solenoid valve assembly out of the unit.
- Insert the O-rings into both adapters.
- Attach the check valve to the manifold and Y-adapter, then install the 2 L-clips.
- Place the back cover on the WEC and secure with 11 screws.
Applies to: WEC600
More general guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien WEC service manual, p. 100-101. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.