Navien · General troubleshooting
Replace the post carbon block (C/B) cartridge
What is going on
Procedure for changing the post carbon block filter. Replace about every 6 months, or sooner based on water quality or flow loss.
Likely causes
- Flow or pressure loss at fixtures may mean the cartridge needs changing before the indicator comes on.
- Water quality can shorten cartridge life.
Check in this order
- Unplug the WEC power cord (power off). An error will block filter replacement if power is still on.
- Close the inlet and outlet valves.
- Open the bypass valve.
- Press the red pressure release button on the post C/B housing cover. If there is no button, use the same bypass, outlet and faucet method described for the sediment filter.
- Unscrew the housing with the filter housing wrench.
- Remove and discard the used cartridge.
- Clean inside the housing.
- Install the new cartridge with the top gaskets in place and centered, then tighten.
- Close bypass and outlet valves, then open inlet and service valves.
- Press the red pressure release button to purge air.
- If flushing through the service line, open the service valve and drain for 3 minutes. The cartridge may release fine black powder during this first flush.
- Close bypass and service valves, then open inlet and outlet valves.
- Plug the power cord in. The WEC starts Auto Flushing and then goes to standby.
- Reset the post C/B filter use period press and hold Back, OK and Next for 3 seconds (see 3.7, p. 36).
- Keep the inlet and outlet plugs in place until installation. Do not leave internals exposed to air for more than 4 hours.
Applies to: WEC Series post carbon block (C/B) filter
More general guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien WEC Series Service Manual, p. 44-45. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.