Replace the freeze prevention solenoid valve
What is going on
Replacement procedure for the freeze prevention solenoid valve on the WEC600. Work from the back of the unit with the feedwater off and power disconnected. Remove the back cover first (see page 82 of the manual, not included in this extract).
Check in this order
- Turn off the feedwater supply.
- Disconnect the power supply from the WEC.
- Remove the back cover from the WEC.
- Remove the 2 screws holding the freeze prevention solenoid valve and pull the valve out.
- Disconnect the valve connector.
- Remove the 2 clips and detach the hoses from the valve.
- Connect the hoses to the new valve and secure with the 2 clips.
- Connect the harness connector to the new valve.
- Set the valve in place and secure with the 2 screws.
- Put the back cover on and secure with 11 screws.
Applies to: WEC600
More general guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien WEC service manual, p. 96. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.