Navien · General troubleshooting

Removing the CIP tank assembly

WEC

What is going on

Pull the CIP tank out of the WEC600 without spilling the cleaning solution.

Check in this order

  1. Remove the 4 screws holding the CIP tank.
  2. Release the 2 clips on the CIP dosing pump.
  3. Pull the CIP tank assembly out of the WEC carefully so no solution spills or overflows.
  4. Set the CIP tank on a flat, clear surface.
  5. From the back of the tank, disconnect the water level sensor connector and the CIP dosing pump connector from the harness.
  6. Remove the CIP outlet hose from the CIP dosing pump.
  7. If CIP solution contacts skin or eyes, rinse immediately with flowing water.

Applies to: WEC600

More general guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien WEC service manual, p. 112. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.