Navien · General troubleshooting
Pre-treatment filters for poor feedwater
What is going on
Extra filtration is required when turbidity or iron is above the limits. The sediment pre-filter must sit on the point-of-entry line ahead of the WEC.
Likely causes
- Turbidity above the EPA standard
- Total iron above 0.3 ppm
Check in this order
- If turbidity exceeds the EPA standard (≤ 0.3 NTU at 95% and ≤ 1 NTU), install an extra filter upstream of the sediment pre-filter.
- If total iron is over 0.3 ppm, install an iron filter before the sediment pre-filter.
- Install the sediment pre-filter on the POE line before the WEC.
- Do not connect the sediment pre-filter directly to the WEC inlet.
- Confirm the sediment pre-filter and post carbon block filter are installed correctly.
Applies to: WEC600
More general guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: WEC Series service manual, p. 16. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.