Viessmann · General troubleshooting
Piping layout with primary heat pump and optional backup heater
What is going on
The tank acts as a hydraulic buffer between the heat pump, the backup heat generator and the system loop.
Check in this order
- Connect the system return to the tank system return port (H).
- Connect the system supply from the highest point port (J) to the system.
- Connect the primary heat/cool generator supply to port D and its return to port G at the lowest point.
- If a backup heat generator is used, connect its supply to port B and its return to port I.
- Leave the injection process plug (F) closed and unconnected.
- Verify all piping and componentry in the field; the drawing is conceptual only.
Applies to: Vitocell 100-E MSCA-20-S2 with Vitocal 100-AW AM2V
More general guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocell 100-E MSCA-20-S2 Technical Data Manual, p. 6-7. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.