Check network and Internet requirements before commissioning

Vitoconnect

What is going on

The Vitoconnect needs a Wi-Fi router, a permanent flat-rate Internet connection and specific open ports. An IT professional should confirm the network on site.

Check in this order

  1. Confirm the Wi-Fi router has Wi-Fi enabled and is protected with WPA2. Unencrypted connections are discouraged.
  2. Confirm a flat-rate Internet connection with high availability is available, so the Vitoconnect stays connected to the Viessmann server.
  3. Confirm the network uses dynamic IP addressing (DHCP), as delivered.
  4. Have an IT professional open outgoing ports 80, 123, 443 and 8883 on the LAN, and set up routing and security if needed.
  5. Note that the Vitoconnect cannot connect to other servers.

Applies to: Vitoconnect OPTO2 with Wi-Fi router

More general guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitoconnect OPTO2 Installation and Operating Instructions, p. 7. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.