Viessmann · General troubleshooting
Choosing the remote control mounting location
What is going on
Mount the remote unit where its built-in room sensor reads the living-space temperature correctly. Keep it away from direct sun, fireplaces, TVs, windows, doors and radiators. Radiator thermostatic valves in the same room must stay fully open. Do not install other controllers in that room.
Check in this order
- Mount on an internal wall in the living space, about 5 ft (1.5 m) above the floor.
- Keep it clear of windows, doors, radiators and direct heat sources.
- Fully open any thermostatic radiator valves in the same room.
- Do not add another controller in the same room.
Applies to: Room temperature dependent control
More general guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotrol 300A installation and service instructions, p. 4. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.