Configure BACnet/IP settings on the gateway
What is going on
Set up the gateway over a direct connection to a computer before joining it to the BMS network.
Check in this order
- Connect your computer directly to the gateway's BACnet interface with no other devices on the link (isolated network).
- Set the computer to automatic IP (DHCP), or set its IP address to 192.168.88.90 with subnet mask 255.255.255.0.
- Restart the gateway by cycling power off and on.
- Open a browser and go to http://192.168.88.89/admin.
- Log in with the default user name and password 'admin' (change it on the Change Password screen).
- Open the Configuration pages and set the BACnet Device Settings, pressing SAVE on each screen you change.
- Confirm the Activate Configuration screen and choose SAVE to store settings; the gateway reboots automatically.
- Once rebooted, join the gateway to the network without duplicating an IP address already in use, then access the configuration pages via 192.168.88.89 or the newly assigned address.
Applies to: Versatronik 535 Solar gateway, BACnet IP
More general guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Versatronik 535 Solar BACnet IP manual, p. 12, 13. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.