No response from the gateway over Modbus

Versatronik 522 OT

What is going on

The BMS master gets no reply from the gateway.

Likely causes

  • Serial settings do not match the gateway
  • Address dial is between two positions
  • Communication cable polarity is reversed

Check in this order

  1. Set the master to 9600 baud, 8 data bits, no parity, 1 stop bit (8-N-1 RTU).
  2. Check that the rotary address dial sits exactly on position 0 or 1-9.
  3. Check that the + and - wires match polarity at the adapter and at the RS485 network.

Applies to: Versatronik 522 OT Modbus gateway

More general guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik 522 OT Modbus manual, p. 10. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.