Viessmann · General troubleshooting
No response from the gateway over Modbus
What is going on
The BMS master gets no reply from the gateway.
Likely causes
- Serial settings do not match the gateway
- Address dial is between two positions
- Communication cable polarity is reversed
Check in this order
- Set the master to 9600 baud, 8 data bits, no parity, 1 stop bit (8-N-1 RTU).
- Check that the rotary address dial sits exactly on position 0 or 1-9.
- Check that the + and - wires match polarity at the adapter and at the RS485 network.
Applies to: Versatronik 522 OT Modbus gateway
More general guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Versatronik 522 OT Modbus manual, p. 10. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.