Neutralizer maintenance and media replacement

Light Commercial Neutralizer

What is going on

Check the neutralizing media and pH at the outlet on a regular schedule.

Check in this order

  1. Make sure the outlet discharge can be accessed for testing.
  2. Check the media level in the unit periodically.
  3. Check the pH at the outlet once a year using pH test strips or an electronic pH meter.
  4. Replace the media when the pH drops below the local water authority minimum.
  5. Replace the media when pH falls below 6.0.
  6. Order replacement media GXXX001328 from Navien or a local Navien dealer.

Applies to: Light Commercial Neutralizer GXXX001324

More general guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Light Commercial Neutralizer installation instructions, p. 2. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.