Navien · General troubleshooting
Neutralizer maintenance and media replacement
What is going on
Check the neutralizing media and pH at the outlet on a regular schedule.
Check in this order
- Make sure the outlet discharge can be accessed for testing.
- Check the media level in the unit periodically.
- Check the pH at the outlet once a year using pH test strips or an electronic pH meter.
- Replace the media when the pH drops below the local water authority minimum.
- Replace the media when pH falls below 6.0.
- Order replacement media GXXX001328 from Navien or a local Navien dealer.
Applies to: Light Commercial Neutralizer GXXX001324
More general guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Light Commercial Neutralizer installation instructions, p. 2. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.