Monthly maintenance of the neutralizer tank

Commercial Condensate Neutralizer

What is going on

The tank must be checked monthly and the media changed on schedule so condensate stays neutral enough to protect drains and the public sewer.

Likely causes

  • Media exhausted or coated with precipitate
  • Debris blocking the flow path
  • Condensate pH dropped below the local minimum

Check in this order

  1. Once a month, check the tank for cleanliness, media level and pH.
  2. Remove any precipitate coating or debris to prevent blockages.
  3. Check pH after condensate leaves the tank, or remove the lid and sample from the last chamber before the outlet.
  4. Use pH test strip paper or an electronic pH meter for an accurate reading.
  5. Replace the neutralizing media when pH falls below the local water authority minimum, or after one year, whichever comes first.
  6. For replacement media, contact the local Navien distributor.

Applies to: Commercial condensate neutralizer tank

More general guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Commercial condensate neutralizer tank installation instructions, p. 1. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.