Navien · General troubleshooting

Monthly maintenance and media replacement

Large Commercial Condensate Neutralizer Tank

What is going on

Check the tank monthly for debris, media level and pH. Replace the neutralizing media when pH falls below the local minimum or after one year, whichever comes first.

Check in this order

  1. Once a month, check the tank for cleanliness and remove any debris to prevent blockages.
  2. Check the neutralizing media level.
  3. Check condensate pH after it leaves the tank, or lift the lid and sample from the last chamber before the outlet.
  4. Use pH test strip paper or an electronic pH meter for an accurate reading.
  5. Replace the neutralizing media when pH drops below the local water authority minimum, or after one year, whichever comes first.
  6. Order replacement media from a local Navien distributor (Replacement Media #GXXX002369).

Applies to: Large commercial condensate neutralizer tank, 7,000 MBTU/hr

More general guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien large commercial condensate neutralizer tank installation instructions, p. 1. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.