Viessmann · General troubleshooting
Make the RJ45 communication cable (supplied cable)
What is going on
Prepare the supplied UTP cable so it connects the gateway to the solar control, using only wires 1 and 2.
Check in this order
- Cut the UTP cable to 2 m.
- Strip the insulation and crimp an RJ45 plug on one end.
- On the other end, strip the jacket and cut all wires except wires 1 and 2.
- Strip wires 1 and 2.
- Connect wires 1 and 2 to the solar control.
Applies to: Versatronik 535 Solar gateway, RJ45 communication cable
More general guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Versatronik 535 Solar BACnet IP manual, p. 6. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.