Gateway does not answer the BMS over Modbus

Versatronik

What is going on

No response from the gateway when the BMS polls it.

Likely causes

  • Serial port on the BMS is not set to 9600 8-N-1.
  • Rotary address dial is between two positions instead of on a number.
  • RS-485 A and B wires are reversed.

Check in this order

  1. Set the BMS port to 9600 baud, 8 data bits, no parity, 1 stop bit.
  2. Turn the rotary address dial fully onto a number from 1 to 9.
  3. Check that the A and B communication wires match polarity at both ends.

Applies to: Versatronik 532 Solar/Modbus and 532D Solar/Modbus gateways

More general guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik 532 Solar/Modbus manual, p. 12. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.