Gateway does not answer the BMS over Modbus
What is going on
No response from the gateway when the BMS polls it.
Likely causes
- Serial port on the BMS is not set to 9600 8-N-1.
- Rotary address dial is between two positions instead of on a number.
- RS-485 A and B wires are reversed.
Check in this order
- Set the BMS port to 9600 baud, 8 data bits, no parity, 1 stop bit.
- Turn the rotary address dial fully onto a number from 1 to 9.
- Check that the A and B communication wires match polarity at both ends.
Applies to: Versatronik 532 Solar/Modbus and 532D Solar/Modbus gateways
More general guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Versatronik 532 Solar/Modbus manual, p. 12. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.