Navien · General troubleshooting
Draining the water from the WEC
What is going on
Drain the unit through the drain connector on the inlet water pipe assembly.
Check in this order
- Remove the front cover (see front cover procedure)
- Disconnect the clip and end plug from the drain connector of the inlet water pipe assembly
- Connect the drain hose to the drain connector
- Wait until the water is fully drained from the WEC
- Reassemble in reverse order
Applies to: WEC600
More general guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien WEC600 service manual, p. 81-82. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.