Condensate piping and backflow prevention

Light Commercial Neutralizer

What is going on

Pipe the condensate so it drains freely and cannot flow back into the appliance.

Check in this order

  1. Use corrosion-resistant pipe materials for the neutralizer and drain lines.
  2. Wrap Teflon tape on all threaded plastic fittings.
  3. Secure drain piping to the floor with clamps so it cannot move.
  4. Install unions at each neutralizer connection so the unit can be removed for service.
  5. Make sure the bottom of the appliance condensate outlet sits above the bottom of the neutralizer outlet.
  6. Make sure no condensate can flow back into the appliance.
  7. Keep condensate lines out of freezing areas. Protect lines in traffic areas.
  8. Route the neutralizer outlet to a floor drain or other approved drain.
  9. If used, place the optional Y-fitting at least 2 in above the neutralizer and run the overflow line below the condensate drain line. End the overflow line where its flow is easy to see.

Applies to: Light Commercial Neutralizer GXXX001324

More general guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Light Commercial Neutralizer installation instructions, p. 2. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.