Navien · General troubleshooting
Condensate piping and backflow prevention
What is going on
Pipe the condensate so it drains freely and cannot flow back into the appliance.
Check in this order
- Use corrosion-resistant pipe materials for the neutralizer and drain lines.
- Wrap Teflon tape on all threaded plastic fittings.
- Secure drain piping to the floor with clamps so it cannot move.
- Install unions at each neutralizer connection so the unit can be removed for service.
- Make sure the bottom of the appliance condensate outlet sits above the bottom of the neutralizer outlet.
- Make sure no condensate can flow back into the appliance.
- Keep condensate lines out of freezing areas. Protect lines in traffic areas.
- Route the neutralizer outlet to a floor drain or other approved drain.
- If used, place the optional Y-fitting at least 2 in above the neutralizer and run the overflow line below the condensate drain line. End the overflow line where its flow is easy to see.
Applies to: Light Commercial Neutralizer GXXX001324
More general guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Light Commercial Neutralizer installation instructions, p. 2. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.