Goodman · Furnace troubleshooting
Upflow vertical - drain exiting left side
What is going on
Routing the condensate drain out the left side of an upflow furnace uses a hose and fitting kit. The hose cut point depends on the cabinet width, so measure and confirm before cutting.
Likely causes
- Furnace installed with the drain on the left side
- Hose cut at the wrong line for the cabinet width
- Clamp loose or wrong size, leaking
- Fitting installed backwards, barb outside
Check in this order
- Install the 45 degree pipe/hose coupling through the left side hole, barb end inside. Secure with two #8 self-tapping screws.
- Cut hose #3 at line B for a 17.5 in cabinet, at line C for a 21 in cabinet, or do not cut for a D width cabinet. Confirm the cabinet width first.
- Connect the large end of hose #3 to the trap outlet with a 1.25 in clamp.
- Connect the small end of hose #3 to the 45 degree elbow with a 1 in clamp.
- Connect the field drain to the furnace trap outlet per the field drain section.
- Pour water through and check for leaks at the clamps.
Applies to: Upflow vertical, left side drain
More furnace guides
- Airflow lower than demanded, furnace runs on low stage when high stage is expected
- Alternate combustion air opening (upflow or horizontal)
- Alternate vent/flue location (upflow or horizontal left)
- Annual inspection checklist
- Auxiliary limit control (location and purpose)
- Auxiliary limit switch open (blower compartment)
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Goodman GMVC96 service manual, p. 21. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.