Goodman · Furnace troubleshooting

Upflow vertical - drain exiting left side

34.5 in Chassis ACVC96/AMVC96/GCVC96/GMVC96

What is going on

Routing the condensate drain out the left side of an upflow furnace uses a hose and fitting kit. The hose cut point depends on the cabinet width, so measure and confirm before cutting.

Likely causes

  • Furnace installed with the drain on the left side
  • Hose cut at the wrong line for the cabinet width
  • Clamp loose or wrong size, leaking
  • Fitting installed backwards, barb outside

Check in this order

  1. Install the 45 degree pipe/hose coupling through the left side hole, barb end inside. Secure with two #8 self-tapping screws.
  2. Cut hose #3 at line B for a 17.5 in cabinet, at line C for a 21 in cabinet, or do not cut for a D width cabinet. Confirm the cabinet width first.
  3. Connect the large end of hose #3 to the trap outlet with a 1.25 in clamp.
  4. Connect the small end of hose #3 to the 45 degree elbow with a 1 in clamp.
  5. Connect the field drain to the furnace trap outlet per the field drain section.
  6. Pour water through and check for leaks at the clamps.

Applies to: Upflow vertical, left side drain

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Goodman GMVC96 service manual, p. 21. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.