Goodman · Furnace troubleshooting

Alternate vent/flue location (upflow or horizontal left)

ACVC96/AMVC96/GCVC96/GMVC96

What is going on

The alternate vent exit is the large hole in line with the induced draft blower outlet. It is not available on counterflow models.

Likely causes

  • Vent pipe condensate entering the draft inducer housing in horizontal left installs

Check in this order

  1. Remove the four screws from the vent pipe flange on top of the furnace.
  2. Remove the internal elbow and vent pipe.
  3. Cut 2 1/2 in. from the flange.
  4. Remove the plastic plug in line with the inducer outlet.
  5. Install the cut flange section and connect it to the inducer with the supplied rubber coupling.
  6. Reinstall the flange with the screws removed in step 1.
  7. In horizontal left, provide condensate collection so vent condensate does not enter the inducer housing. If the vent drain elbow is removed, use an RF000142 kit.
  8. Do not damage internal wiring or components when reinstalling the coupling and screws.

Applies to: Upflow and horizontal left installations

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Goodman GMVC96 service and troubleshooting manual, p. 15. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.