Goodman · technician tips
Goodman service menus, test modes and resets
63 tips for air conditioner, air handler, furnace: access codes, button combinations, test modes and the resets you need at the appliance.
Jump to: Access & passwords (3) · Button combinations (1) · Service & test modes (7) · Reset & cancel (8) · Settings shortcuts (2) · Commissioning (13) · Other (29)
Access & passwords
Installer and service menu codes, and how to get into them.
App access code and alternate connection
Furnace · ACVC96, AMVC96, GCVC96, GMVC96
The app asks for a 3-digit access code shown on the three 7-segment displays, visible through the sight glass near the board. Three wrong entries cause a new code to show. Option 2 is to remove the door and read the digits with power on. This power cycles the control, and the code stays active briefly after a power cycle.
- Read the 3-digit code through the sight glass, or remove the door with power on and read it there.
- Enter the code in the app when prompted.
- If the code is entered wrong three times, a new code appears on the control; read the new code.
- Use the thermostat task method instead if you do not want to power cycle the control.
Applies to: All 34.5in chassis furnaces with CoolCloud app
Source: Goodman GMVC96 service and troubleshooting manual, p. 33. Written in our own words; check the manual for your exact model.
Unit address shown at power-up
Furnace · ACVC96, AMVC96, GCVC96, GMVC96
At power-up the control shows the unit address as a two-digit number on the 2nd and 3rd 7-segment characters. After start-up it moves to the Status Menu.
- Apply power and watch the 2nd and 3rd digits for the unit address during start-up.
Applies to: All 34.5in chassis furnaces
Source: Goodman GMVC96 service and troubleshooting manual, p. 33. Written in our own words; check the manual for your exact model.
Button combinations
Key presses that open menus, show readouts or switch modes.
Service & test modes
Forced fan, low and high fire, test and diagnostic modes, error history and live data.
Run the R-32 leak alarm test (RDS test mode)
Air handler · Goodman/Amana R-32 AMST/AWSF/ACSF air handlers
Simulates an R-32 leak alarm for 5 minutes to prove the system reacts; the red LED flashes fast as in a real alarm.
- Press the manual test button on the control board 2 times within 5 seconds
- The LED flashes fast and the control acts as if a leak were detected
- The test ends by itself after 5 minutes, or press the button once to stop it early
Applies to: AMST/AWSF/ACSF R-32 air handlers
Source: R-32 GLXS/GLZS and AMST/AWSF service RS6200301, RDS A2L PCB FAULT CODE table p.25 and Recommended Action table p.26. Written in our own words; check the manual for your exact model.
Gas pressure test mode (100% firing)
Furnace · ACVC96, AMVC96, GCVC96, GMVC96
The gas pressure test menu locks the burner at 100% firing rate so gas valve pressure can be checked. Inlet supply pressure must match the unit rating plate with all other household gas appliances running.
- Enter the Gas Pressure Test menu to lock 100% firing rate.
- Measure gas valve pressure while the burner is at full fire.
- Confirm inlet supply pressure matches the rating plate with other gas appliances running.
- Leave the test mode when finished.
Applies to: All 34.5in chassis furnaces
Source: Goodman GMVC96 service and troubleshooting manual, p. 35. Written in our own words; check the manual for your exact model.
High fire and low fire gas pressure test (longer term)
Furnace · A/GMVC96, A/GCVC96
Forces a continuous high fire or low fire run using thermostat W. Remove the communicating or RJ12 connection first as described.
- Turn the furnace off.
- On a communicating fossil fuel system, remove or disconnect anything on terminals 1, 2, R and C. With a non-communicating heat pump module, unplug the RJ12 jack.
- Power the furnace.
- High fire: apply a W call. The system runs continuously at 100% firing. Remove W to shut down.
- Low fire: apply W, let ignition start, then remove W so the furnace enters idle (display shows IdL).
- Apply W again. Low stage runs for more than 5 minutes if the target run time is set above 10 minutes.
- Remove W to shut down when done.
Applies to: Gas pressure test, high and low fire
Source: Goodman GMVC96 service manual, p. 52. Written in our own words; check the manual for your exact model.
High fire gas pressure test (temporary)
Furnace · A/GMVC96, A/GCVC96
Runs high fire for a short time from the on-board buttons. The CoolCloud app is preferred for functional tests.
- Use the on-board buttons to enter the Gas Pressure Test menu (display shows gPt).
- Select YES to enable the test.
- High fire runs for 5 minutes or until any of the 3 buttons is pressed.
Applies to: Gas pressure test, high fire
Source: Goodman GMVC96 service manual, p. 52. Written in our own words; check the manual for your exact model.
Testing gas heat only with a heat pump installed
Furnace · 34.5 in chassis ACVC96/AMVC96/GCVC96/GMVC96
With a heat pump installed, the system may stage between heat pump and furnace during a heat test.
- Disconnect communications between the indoor and outdoor units.
- Run the heating test to check gas heat only.
Applies to: Furnace with communicating outdoor unit
Source: Goodman GMVC96 service and troubleshooting manual, p. 26. Written in our own words; check the manual for your exact model.
View and clear the last 6 furnace faults
Furnace · Goodman/Amana *MVC95/*CVC9 two-stage ComfortNet
The furnace keeps its last six faults, newest first. The same fault repeating is stored only 3 times in a row.
- Open the furnace advanced menus from the ComfortNet thermostat.
- Go to DIAGNOSTICS: FAULT #1 is the newest, FAULT #6 the oldest.
- Set CLEAR to YES to wipe the history. Clear it after you finish a service call.
Applies to: GMVC95/AMVC95 upflow and *CVC9 counterflow two-stage furnaces
Source: Goodman *CVC9/95 & *MVC95 Installation Instructions IO-341D (08/2010), Diagnostics p.45-46. Written in our own words; check the manual for your exact model.
Reset & cancel
Clearing lockouts, service reminders and fault history; skipping purge or de-air programs.
Restart indoor-outdoor communication (Lrn)
Air handler · Goodman/Amana ComfortBridge AVPTC/MBVC
The Lrn menu action restarts communication between the indoor and outdoor units.
- Scroll to Lrn with the Left or Right button
- Press the Center button to select it
Applies to: AVPTC / MBVC ComfortBridge air handlers
Source: Goodman ComfortNet ASXC-DSXC-GSXC / ASZC-DSZC-GSZC / AVPTC-MBVC service, Air Handler Display (B*) menu table pp.61-62 and Menu Navigation p.64. Written in our own words; check the manual for your exact model.
View and clear the 6 most recent faults (FCL / L6F)
Air handler · Goodman/Amana ComfortBridge AVPTC/MBVC
On communicating systems the FCL menu item (labelled L6F in the furnace-style menu) shows the 6 most recent faults and lets you clear them.
- Use the Left or Right button to scroll to FCL
- Press the Center button to enter the menu and read the codes
- Clear them from the same menu if wanted
Applies to: AVPTC / MBVC ComfortBridge air handlers
Source: Goodman ComfortNet ASXC-DSXC-GSXC / ASZC-DSZC-GSZC / AVPTC-MBVC service, Air Handler Display (B*) menu table pp.61-62 and Menu Navigation p.64. Written in our own words; check the manual for your exact model.
Clear an E0 lockout (3 ways)
Furnace · Goodman/Amana *MVC95/*CVC9 two-stage ComfortNet
Lockout after 3 failed ignition tries clears in any of these ways.
- Wait: the control resets itself after 1 hour.
- Cut 115 V power to the furnace and restore it.
- Turn the thermostat down so there is no heat call for 1-20 seconds, then set it back.
- If the fault is still there, it goes straight back into lockout.
Applies to: GMVC95/AMVC95 upflow and *CVC9 counterflow two-stage furnaces
Source: Goodman *CVC9/95 & *MVC95 Installation Instructions IO-341D (08/2010), Resetting from Lockout p.50. Written in our own words; check the manual for your exact model.
Clearing the fault history
Furnace · ACVC96, AMVC96, GCVC96, GMVC96
In the Last 6 Faults menu, press and hold Center for 5 seconds. This clears all non-active faults in that menu. The display flashes three times to confirm. Clear the history during maintenance or service.
- Enter the Last 6 Faults (L6F) menu.
- Press and hold Center for 5 seconds.
- Watch for three flashes to confirm the faults were cleared.
Applies to: All 34.5in chassis furnaces
Source: Goodman GMVC96 service and troubleshooting manual, p. 35. Written in our own words; check the manual for your exact model.
Reset the ComfortNet network (learn button)
Furnace · Goodman/Amana *MVC95/*CVC9 two-stage ComfortNet
The learn button on the furnace control resets communication.
- Press once quickly = power-up reset.
- Hold about 2 seconds = out-of-box reset.
- The red LED shows 2 flashes while it resets.
Applies to: GMVC95/AMVC95 upflow and *CVC9 counterflow two-stage furnaces
Source: Goodman *CVC9/95 & *MVC95 Installation Instructions IO-341D (08/2010), Network Troubleshooting p.47. Written in our own words; check the manual for your exact model.
Reset the furnace control to factory defaults (rFd)
Furnace · Goodman/Amana GM9S96/AM9S96, Goodman/Amana GM9S80/AM9S80, Goodman/Amana GM9C96/AM9C96
The rFd menu item returns the control menu settings to factory defaults.
- Press the left or right switch until rFd shows
- Press the center switch, pick yes or no with the left or right switch
- Press the center switch to confirm
Applies to: GM9S96/AM9S96, GM9S80/AM9S80 and GM9C96/AM9C96 furnaces (7-segment control)
Source: GM9S96 service RS6612022r1, LED Display Menu p.27 and chart p.29; GM9S80 service RS6621008r2, LED Display Menu p.30 and chart p.32; GM9C96 service RS6612020r1, LED Display Menu p.33 and chart p.35. Written in our own words; check the manual for your exact model.
Resetting a furnace lockout
Furnace · ACVC96, AMVC96, GCVC96, GMVC96
Lockout happens when the furnace fails to ignite after three attempts in one call for heat. The furnace stops and shows a lockout code on the 7-segment display. The control resets automatically one hour after lockout. A manual reset is also possible.
- Wait one hour for the automatic reset, or
- Interrupt 115 VAC power to the furnace to reset manually, or
- Lower the thermostat so there is no call for heat for 1 to 20 seconds to reset manually.
Applies to: All 34.5in chassis gas furnaces
Source: Goodman GMVC96 service and troubleshooting manual, p. 37. Written in our own words; check the manual for your exact model.
View and clear the last 6 stored faults (L6F)
Furnace · Goodman/Amana GM9S96/AM9S96, Goodman/Amana GM9S80/AM9S80, Goodman/Amana GM9C96/AM9C96
The L6F menu item lists the last 6 fault codes, newest first. Read the stored code through the sight glass before opening the blower door, since opening it without holding the door switch closed erases the stored code.
- Press the left or right switch until L6F shows
- Press the center switch and read the stored faults
- To erase them, keep the center switch pressed for 5 to 30 seconds; the display blinks three dashes three times, then shows L6F again
Applies to: GM9S96/AM9S96, GM9S80/AM9S80 and GM9C96/AM9C96 furnaces (7-segment control)
Source: GM9S96 service RS6612022r1, LED Display Menu p.27 and chart p.29; GM9S80 service RS6621008r2, LED Display Menu p.30 and chart p.32; GM9C96 service RS6612020r1, LED Display Menu p.33 and chart p.35. Written in our own words; check the manual for your exact model.
Settings shortcuts
Where the useful parameters live and what they are set to from the factory.
Turn on dehumidification
Furnace · Goodman/Amana *MVC95/*CVC9 two-stage ComfortNet
Blower drops to about 82% of the cooling speed on a combined cool + dehumidify call.
- Power off.
- Wire a 24 V dehumidistat that opens on humidity rise: neutral to DEHUM, hot to R, ground to the junction box screw.
- Set S5 switch 9 ON.
- On non-communicating systems jumper Y1 to DEHUM (and Y1 to O for ramping profiles).
- Power back on.
Applies to: GMVC95/AMVC95 upflow and *CVC9 counterflow two-stage furnaces
Source: Goodman *CVC9/95 & *MVC95 Installation Instructions IO-341D (08/2010), 24 Volt Dehumidistat Wiring p.29; Thermostat Wiring p.28; DIP Switches p.52. Written in our own words; check the manual for your exact model.
Use a single-stage thermostat (timed staging)
Furnace · Goodman/Amana *MVC95/*CVC9 two-stage ComfortNet
With a single-stage stat the furnace runs low fire first and steps to high fire on a timer.
- Power off.
- S1 switch 3 OFF = single-stage thermostat (ON = two-stage).
- S1 switch 4 OFF = fixed 5 minute step-up, ON = auto (1-12 minutes based on the last 3 cycles).
- Power back on.
Applies to: GMVC95/AMVC95 upflow and *CVC9 counterflow two-stage furnaces
Source: Goodman *CVC9/95 & *MVC95 Installation Instructions IO-341D (08/2010), Single-Stage Thermostat Application p.28-29; DIP Switches p.52. Written in our own words; check the manual for your exact model.
Commissioning
Start-up and set-up steps that are easy to miss.
Charging the outdoor unit
Air conditioner · 34.5 in chassis ACVC96/AMVC96/GCVC96/GMVC96
A cooling call right after power-up runs the outdoor unit at full capacity, which is useful for charging.
- Turn on power to the indoor and outdoor units.
- Give a cooling call (Y or Y+G).
- The outdoor unit runs at full capacity until the call is removed.
- If the system runs in low stage, cycle power and give the cool call again to get full capacity.
Applies to: Communicating two stage or inverter outdoor units
Source: Goodman GMVC96 service and troubleshooting manual, p. 25-26. Written in our own words; check the manual for your exact model.
Airflow setup for communicating and non-communicating outdoor units
Furnace · 34.5 in chassis ACVC96/AMVC96/GCVC96/GMVC96
A communicating outdoor unit sets indoor airflow itself. A non-communicating outdoor unit needs airflow set by tonnage.
- Communicating outdoor unit: no main airflow adjustment is needed. Airflow trims can be made if wanted.
- Non-communicating outdoor unit: find the desired airflow, using 350 to 450 CFM per ton with 400 CFM per ton as the standard.
- Select the tonnage closest to the desired airflow in the tonnage menu. Trim is available for fine adjustment.
Applies to: Communicating and non-communicating outdoor units
Source: Goodman GMVC96 service and troubleshooting manual, p. 27, 29. Written in our own words; check the manual for your exact model.
Allowed installation positions
Furnace · ACVC96/AMVC96/GCVC96/GMVC96
The furnace can be installed upright or horizontal on the left or right side panel. Never install it on its back. Return ductwork goes to the side panels and/or basepan on upright upflow units, and to the basepan on horizontal upflow and counterflow units. Never attach ductwork to the back of the furnace.
- Select an upright or horizontal position per the recommended positions figure.
- Attach return ductwork only to the allowed panels or basepan.
- Do not attach any duct to the rear of the cabinet.
Applies to: Upflow and counterflow models
Source: Goodman GMVC96 service and troubleshooting manual, p. 9. Written in our own words; check the manual for your exact model.
Dual certification: non-direct and direct vent
Furnace · ACVC96/AMVC96/GCVC96/GMVC96
The furnace can be installed as non-direct vent (one pipe, vent only) or direct vent (two pipes, vent plus combustion air intake). Use the section for the chosen type for pipe size, length, elbows and terminations.
- Decide between non-direct vent (single pipe) and direct vent (dual pipe).
- Follow the matching section for piping size, length, elbows and terminations.
Applies to: Dual-certified MVC96/CVC96 models
Source: Goodman GMVC96 service and troubleshooting manual, p. 11. Written in our own words; check the manual for your exact model.
High altitude application (USA)
Furnace · A/GMVC96, A/GCVC96
Install the correct high altitude orifice or pressure switch kit for the altitude and gas type. Kits are chosen by installation altitude and natural or propane use. Do not derate by lowering manifold pressure below the rating plate.
- Select the orifice or pressure switch kit using the altitude range table in the technical manual or spec sheet.
- Choose the kit for natural or propane gas.
- If the gas supplier derates the gas, size the orifice from the derated BTU/ft³ and altitude per NFPA 54 / ANSI Z223.1 and supplier data.
- Do not lower manifold pressure below the rating plate value to compensate.
Applies to: High altitude installs
Source: Goodman GMVC96 service manual, p. 53-54. Written in our own words; check the manual for your exact model.
Minimum clearances and service access
Furnace · ACVC96/AMVC96/GCVC96/GMVC96
Keep the printed clearances to combustible materials on the unit label, and always allow 24 in. of front service clearance. Pipe and wiring connections can need more room than the minimum. Where accessibility clearance is larger than an enclosure clearance, the larger one wins. The clearance table on this page has jumbled column alignment in this file, so take the exact numbers from the unit label or the printed clearance figure.
- Check the unit clearance label for the position (upflow, counterflow or horizontal).
- Confirm 24 in. of front clearance for servicing.
- Allow room for gas, electrical, drain trap and vent/intake connections.
Applies to: CVC96 and MVC96 furnaces, all positions
Source: Goodman GMVC96 service and troubleshooting manual, p. 8. Written in our own words; check the manual for your exact model.
Non-direct vent: intake elbow requirement
Furnace · ACVC96/AMVC96/GCVC96/GMVC96
Non-direct vent needs no intake pipe, but put at least one 90-degree elbow on the combustion air intake to guard against blockage. This applies to upright units on the standard intake or horizontal units on the alternate intake.
- Install at least one 90-degree elbow on the combustion air intake coupling.
Applies to: Non-direct vent installations
Source: Goodman GMVC96 service and troubleshooting manual, pp. 14-15. Written in our own words; check the manual for your exact model.
Pipe slope, support and transitions
Furnace · ACVC96/AMVC96/GCVC96/GMVC96
Support horizontal vent runs every three to five feet with a 1/4 in. per foot downward slope back to the furnace so condensate drains. Avoid a horizontal transition, which creates a water trap. Do not change from 2 in. to 3 in. pipe in a horizontal run. Leave room for expansion, and secure piping well if a long run is followed by an offset under 40 in.
- Support horizontal vent runs every 3 to 5 ft.
- Slope horizontal runs 1/4 in. per foot back toward the furnace.
- Use a transition of no less than 45 degrees to the horizontal plane.
- Do not make a horizontal 2 in. to 3 in. transition.
- Secure piping tightly where a long run ends in an offset under 40 in.
Applies to: Vent/flue piping
Source: Goodman GMVC96 service and troubleshooting manual, p. 12-13. Written in our own words; check the manual for your exact model.
Reload model data with the memory card
Furnace · Goodman/Amana *MVC95/*CVC9 two-stage ComfortNet
Used for d0 / d4 or after a control swap.
- Use the memory card for this exact model.
- Power off, insert the card, power on. Data loads at power-up.
- Power off before removing the card.
Applies to: GMVC95/AMVC95 upflow and *CVC9 counterflow two-stage furnaces
Source: Goodman *CVC9/95 & *MVC95 Installation Instructions IO-341D (08/2010), Troubleshooting Chart p.55-56. Written in our own words; check the manual for your exact model.
Set heat anticipator on room thermostat
Furnace · ACVC96/AMVC96/GCVC96/GMVC96
The room thermostat heat anticipator must match the wiring diagram note for this furnace.
- Set the heat anticipator on the room thermostat to 0.7 amps.
Applies to: ACVC96/AMVC96/GCVC96/GMVC96 furnaces
Source: Goodman GMVC96 service and troubleshooting manual, p. 64. Written in our own words; check the manual for your exact model.
Sharp sheet metal edges
Furnace · ACVC96/AMVC96/GCVC96/GMVC96
Holes in the cabinet can have sharp edges. Wear gloves when removing hole plugs.
- Wear gloves when removing hole plugs from the cabinet.
Applies to: All cabinets
Source: Goodman GMVC96 service and troubleshooting manual, p. 14. Written in our own words; check the manual for your exact model.
Standard furnace vent and intake connections
Furnace · ACVC96/AMVC96/GCVC96/GMVC96
The vent outlet takes 2 in. pipe and is glued into the furnace fitting, or a short 2 in. section can be glued in with a rubber coupling for service removal. Route piping away from refrigerant lines, metering devices and condensate lines. Two 45-degree long-sweep elbows make an offset that counts as one 90-degree elbow.
- Glue the vent pipe into the furnace fitting, or use a short glued section and rubber coupling.
- Route vent and intake pipe clear of refrigerant lines, metering devices and condensate drains.
- Use two 45-degree long-sweep elbows if extra clearance is needed; count as one 90-degree elbow.
Applies to: Vent/flue connections
Source: Goodman GMVC96 service and troubleshooting manual, p. 14. Written in our own words; check the manual for your exact model.
Thermostat setup: single stage heat and cool
Furnace · 34.5 in chassis ACVC96/AMVC96/GCVC96/GMVC96
The furnace needs only Y for cooling and W for heating. Set the thermostat to single stage heat / single stage cool and do not use multi stage mode.
- Set the thermostat to single stage heat / single stage cool.
- Confirm 24VAC on Y for cool calls and on W for heat calls.
- Do not set the thermostat to heat pump mode. The only exception is a non-communicating single stage heat pump, which needs heat pump mode with the reversing valve on in cooling.
- Do not use an O wire; this system has no reversing valve input.
Applies to: All systems with this control
Source: Goodman GMVC96 service and troubleshooting manual, p. 25, 29, 30. Written in our own words; check the manual for your exact model.
Other
Everything else worth knowing at the appliance.
Active alarm display
Furnace · ACVC96, AMVC96, GCVC96, GMVC96
An active alarm appears in the Status Menu as E followed by a two-digit alarm code. Look up the two-digit code in the troubleshooting chart.
- Read the E and two-digit code in the Status Menu.
- Look up the code in the troubleshooting chart at the back of the manual.
Applies to: All 34.5in chassis furnaces
Source: Goodman GMVC96 service and troubleshooting manual, p. 35. Written in our own words; check the manual for your exact model.
Air filter maintenance
Furnace · ACVC96, AMVC96, GCVC96, GMVC96
Never run the furnace without a filter. Dust and lint can build up on internal parts and cause lost efficiency, damage and possible fire. Filters are not shipped with the furnace and must be supplied by the installer. Clean permanent filters or replace disposable ones every two months or as needed, using the same type and size.
- Turn off power to the furnace before removing an upflow or counterflow filter.
- Replace the filter with one of the same type and size.
- Vacuum the blower compartment when the filter is removed, if needed.
Applies to: All 34.5in chassis gas furnaces
Source: Goodman GMVC96 service and troubleshooting manual, p. 38. Written in our own words; check the manual for your exact model.
Alternate electrical, gas and vent connections
Furnace · ACVC96/AMVC96/GCVC96/GMVC96
Electrical and gas lines can enter through either side panel, and on horizontal units through the top or bottom. Horizontal alternate vent setups need the RF000142 vent drain kit.
- Choose the side or top/bottom entry for electrical and gas lines.
- If using the horizontal alternate vent, install the RF000142 vent drain kit.
Applies to: Upflow and horizontal models
Source: Goodman GMVC96 service and troubleshooting manual, p. 10. Written in our own words; check the manual for your exact model.
Auxiliary alarm (condensate) switch wiring
Furnace · ACVC96, AMVC96, GCVC96, GMVC96
The control has a 24VAC Aux Alarm input labeled Condensate for a condensate switch. It can also take compatible CO2 sensors or fire alarm contacts. The default AUX switch is normally closed and opens when the evaporator base pan water level is too high.
- Wire the condensate switch to the Condensate (AUX) input on the control.
- Verify the switch is normally closed when the pan is dry.
Applies to: All 34.5in chassis furnaces
Source: Goodman GMVC96 service and troubleshooting manual, p. 32. Written in our own words; check the manual for your exact model.
Blower door interlock
Furnace · 34.5 in chassis ACVC96/AMVC96/GCVC96/GMVC96
The blower door interlock cuts unit voltage when the door is opened. Do not defeat it.
Applies to: Gas furnace
Source: Goodman GMVC96 service and troubleshooting manual, p. 25. Written in our own words; check the manual for your exact model.
Bypass the inductor to test an ECM motor
Furnace · 34.5 in. chassis ACVC96/AMVC96/GCVC96/GMVC96
The inductor is in the line power supply to the motor. If it has failed, the motor will not run.
- Disconnect the black line wire from the inductor.
- Connect that wire directly to the motor.
- If the motor runs, replace the inductor.
Applies to: 3/4 and 1 HP ECM motors with inductor
Source: Goodman GMVC96 service and troubleshooting manual, p. 44. Written in our own words; check the manual for your exact model.
Combustion and ventilation air
Furnace · ACVC96/AMVC96/GCVC96/GMVC96
Most homes need outside air supplied to the furnace area through grilles or ducts open to the outdoors, an attic or a crawl space. Exhaust fans, dryers and fireplaces that pull air out of the house can cause backdrafting. If other gas appliances share the room, size their combustion air as well.
- Confirm the furnace room has adequate outside combustion and ventilation air.
- Check house depressurization with exhaust appliances running.
- Size air for other gas appliances in the same space per NFPA 54/ANSI Z223.1 or CAN/CSA B149.1-15.
Applies to: All furnace installations
Source: Goodman GMVC96 service and troubleshooting manual, p. 9. Written in our own words; check the manual for your exact model.
ComfortBridge memory chip (last resort)
Furnace · A/GMVC96, A/GCVC96
Use the shared data memory chip only as a last resort. The preferred method is the CoolCloudHVAC app.
- Populate shared data using the CoolCloudHVAC app, Shared Data menu under the Furnace tab.
- Use the memory chip only if the app method is not possible.
Applies to: ComfortBridge furnaces
Source: Goodman GMVC96 service manual, p. 55. Written in our own words; check the manual for your exact model.
Counterflow drain trap clearance
Furnace · 34.5 in chassis ACVC96/AMVC96/GCVC96/GMVC96
A horizontal counterflow installation needs a minimum clearance under the drain trap.
- Keep at least 5 1/2 in of clearance beneath the drain trap.
Applies to: Counterflow model installed horizontally with left side down
Source: Goodman GMVC96 service and troubleshooting manual, p. 24. Written in our own words; check the manual for your exact model.
Dehumidification wiring and logic
Furnace · 34.5 in chassis ACVC96/AMVC96/GCVC96/GMVC96
The Dehum input reduces blower speed to 85% during a cooling plus dehum call. The dehumidistat type sets the Dehum logic.
- Connect the dehumidistat between R and Dehum if using an external dehumidistat. It must run on 24VAC.
- If the dehumidistat opens on a humidity rise, set Dehum logic to Low using the CoolCloud app or push buttons.
- If the dehumidistat closes on a humidity rise, set Dehum logic to High using the CoolCloud app or push buttons.
- If using a thermostat, set it to energize Dehum only when dehumidification is wanted.
Applies to: Systems with Dehum input
Source: Goodman GMVC96 service and troubleshooting manual, p. 30-31. Written in our own words; check the manual for your exact model.
Diagnostics: last six faults storage
Furnace · ACVC96, AMVC96, GCVC96, GMVC96
The diagnostics menu stores the last six faults, newest first. A fault that repeats back to back is stored no more than three times. For example, a clogged return filter tripping the limit repeatedly is stored only three times in a row.
- Open the diagnostics menu to review the last six faults.
- Clear the fault history during maintenance or service.
Applies to: All 34.5in chassis furnaces
Source: Goodman GMVC96 service and troubleshooting manual, p. 36. Written in our own words; check the manual for your exact model.
Drain pan and freeze protection
Furnace · ACVC96/AMVC96/GCVC96/GMVC96
If the furnace sits over a conditioned space, use a drain pan that covers the full area under the furnace and any air conditioning coil. Keep the drain trap and vent piping from freezing, and insulate vent piping that sees freezing temperatures or the outdoors with 1/2 in. closed-cell foam.
- Install a drain pan under the full furnace footprint when installed over conditioned space.
- Insulate vent piping exposed to temperatures below 35 F for long periods with 1/2 in. closed-cell foam.
- Insulate vent piping run outdoors or in unheated areas past the listed terminations.
- Check piping for leaks before insulating.
Applies to: Furnaces installed above conditioned space or exposed to freezing
Source: Goodman GMVC96 service and troubleshooting manual, pp. 10, 13. Written in our own words; check the manual for your exact model.
Electronic air cleaner (EAC) line voltage connection
Furnace · 34.5 in chassis ACVC96/AMVC96/GCVC96/GMVC96
The EAC terminal supplies line voltage to an electronic air cleaner or device that runs with the circulating fan. Maximum load is 1.0 A at 120 VAC.
- Turn off furnace power before installing accessories.
- Connect the hot leg to the EAC terminal and the neutral to the NEUTRAL bus or the junction box neutral.
- Use 1/4 in quick connect terminals.
- Make all line voltage splices inside the furnace junction box.
- Use wire rated at least 105°C if extra line voltage wire is run inside the furnace.
Applies to: Furnace with integrated control module
Source: Goodman GMVC96 service and troubleshooting manual, p. 32, 25. Written in our own words; check the manual for your exact model.
Electrostatic discharge precautions for the integrated control module
Furnace · 34.5 inch chassis gas furnaces (ACVC96, AMVC96, GCVC96, GMVC96)
Equalize your body, the furnace and the control to the same electrostatic potential before touching the control or its wiring. This protects the integrated control module from damage on installed and uninstalled furnaces.
- Disconnect all power to the furnace.
- Touch a clean, unpainted metal surface of the furnace near the control to discharge your body.
- Handle the control or wiring, and avoid moving or shuffling your feet or touching ungrounded objects. If you do, touch metal again before handling the control.
- Discharge yourself to ground before taking a new control out of its packaging, and return old or new controls to their containers before touching anything ungrounded.
Applies to: Integrated control module on all furnaces covered
Source: Goodman GMVC96 service and troubleshooting manual, p. 5. Written in our own words; check the manual for your exact model.
Induced draft and circulator blower motors
Furnace · ACVC96, AMVC96, GCVC96, GMVC96
Bearings in the induced draft and circulator motors are permanently lubricated, so no lubrication is needed. Check motor windings for dust buildup, which can cause overheating, and clean as needed.
- Check motor windings for dust buildup.
- Clean the motor if dust is present.
Applies to: All 34.5in chassis gas furnaces
Source: Goodman GMVC96 service and troubleshooting manual, p. 38. Written in our own words; check the manual for your exact model.
Integrated control module diagnostic LED
Furnace · ACVC96, AMVC96, GCVC96, GMVC96
If the control detects a possible safety concern, it stops the appropriate operation and shows diagnostic information on the LED. Use the error code (letter and number) with the troubleshooting chart at the back of the manual.
- Read the error code on the 7-segment LED.
- Look up the code in the troubleshooting chart.
Applies to: All 34.5in chassis gas furnaces
Source: Goodman GMVC96 service and troubleshooting manual, p. 37. Written in our own words; check the manual for your exact model.
Junction box relocation and wiring rules
Furnace · 34.5 in chassis ACVC96/AMVC96/GCVC96/GMVC96
The junction box is shipped on the left side (right for counterflow). Line voltage can enter through either side panel after relocation.
- Disconnect all power before relocating the junction box.
- Remove the burner compartment door.
- Remove and keep the two screws securing the junction box to the side panel.
- Move the junction box, plugs and grommets to the opposite side panel and secure with the saved screws.
- Use copper replacement wire rated at least 105°C if original harness wire is replaced.
- Label all wires before disconnecting them when servicing controls.
Applies to: Gas furnace
Source: Goodman GMVC96 service and troubleshooting manual, p. 24-25. Written in our own words; check the manual for your exact model.
Line voltage electronic air cleaner (EAC) connection
Furnace · ACVC96, AMVC96, GCVC96, GMVC96
The EAC terminal switches line voltage to an electronic air cleaner or other device that runs with the circulator. Maximum accessory load is 1.0 A at 120 VAC. Use 1/4 in quick connects. Hot goes to the EAC terminal and neutral goes to the NEUTRAL bus or the furnace junction box neutral. Any field line voltage splices must be inside the junction box, and added wire must have a minimum 105 C rating.
- Turn off furnace power before installing the accessory.
- Connect the accessory hot to the EAC terminal and the neutral to the NEUTRAL bus or junction box neutral.
- Make all line voltage splices inside the furnace junction box.
- Follow local codes and the air cleaner maker's mounting and grounding instructions.
Applies to: All 34.5in chassis furnaces with EAC accessory
Source: Goodman GMVC96 service and troubleshooting manual, p. 32. Written in our own words; check the manual for your exact model.
Propane and high altitude conversion notes
Furnace · ACVC96/AMVC96/GCVC96/GMVC96
For propane, an orifice change is needed. The LPLP03 kit is strongly recommended so the furnace will not fire when LP supply pressure is too low. At high altitude, a pressure switch and/or orifice and spring change may be needed. Above 7000 ft, use the specification sheets. In Canada, furnaces are certified only to 4500 ft.
- Change the orifice for propane operation.
- Install the LPLP03 kit on LP conversions.
- At high altitude, check whether the pressure switch and/or orifice/spring kit is required.
- Above 7000 ft, use the specification sheet kits. Canada: certified only to 4500 ft.
Applies to: Propane and high altitude installations
Source: Goodman GMVC96 service and troubleshooting manual, pp. 10-11. Written in our own words; check the manual for your exact model.
Reading the furnace model number
Furnace · 34.5 inch chassis gas furnaces (ACVC96, AMVC96, GCVC96, GMVC96)
The 14-character model number identifies the brand (A = Amana, G = Goodman), configuration (M = upflow/horizontal, C = downflow/horizontal, K = dedicated upflow, D = dedicated downflow), gas valve type (M = modulating, C = 2 stage, H = convertible 2 stage, S = single stage), AFUE rating (80, 92, 96 or 97), input capacity in MBtu/h (030 to 120), and maximum CFM (3 = 1200, 4 = 1600, 5 = 2000). Cabinet width is coded A = 14 in, B = 17.5 in, C = 21 in, D = 24.5 in. The nomenclature layout on the page is jumbled, so confirm any position not listed here against the rating plate.
- Locate the 14-digit model number on the rating plate.
- Match the brand, configuration, gas valve and AFUE characters to the nomenclature key.
- Use the model number, not the file name, when ordering parts or service information.
Applies to: ACVC96, AMVC96, GCVC96, GMVC96 furnaces
Source: Goodman GMVC96 service and troubleshooting manual, p. 4. Written in our own words; check the manual for your exact model.
Safety circuit overview
Furnace · ACVC96, AMVC96, GCVC96, GMVC96
Primary limit: on the partition panel, normally closed, auto reset, watches heat exchanger temperature. Auxiliary limit: near the circulator, normally closed, manual reset, watches blower compartment temperature. Rollout limit: on the burner manifold, normally closed, manual reset, trips if flame is not drawn into the heat exchanger. Pressure switches: normally open (closed in operation), watch induced draft and coil front pressure taps for insufficient airflow or blocked condensate drain. Flame sensor: probe on the burner manifold that uses flame rectification to detect flame.
Applies to: All 34.5in chassis gas furnaces
Source: Goodman GMVC96 service and troubleshooting manual, p. 37. Written in our own words; check the manual for your exact model.
Thermostat mounting location
Furnace · ACVC96/AMVC96/GCVC96/GMVC96
Mount the thermostat about five feet off the floor on an inside wall, away from vibration and with good air circulation. Keep it away from drafts, registers, sun, lights, other appliances, fireplaces, hidden pipes or chimneys, and cold outside walls.
- Pick an inside wall about five feet above the floor.
- Avoid drafts, dead spots, registers, sunlight and heat from fixtures or fireplaces.
- Avoid hidden water pipes, chimneys and unconditioned walls behind the thermostat.
- Follow the thermostat maker's mounting instructions.
Applies to: All ACVC96/AMVC96/GCVC96/GMVC96 installations
Source: Goodman GMVC96 service and troubleshooting manual, p. 8. Written in our own words; check the manual for your exact model.
Thermostat placement
Furnace · 34.5 inch chassis gas furnaces (ACVC96, AMVC96, GCVC96, GMVC96)
Mount the thermostat about five feet above the floor on a vibration-free inside wall with good air circulation. Keep it away from drafts, dead spots behind doors, corners, and areas under supply registers or in direct sun.
- Pick an inside wall with good air movement and no vibration.
- Mount the thermostat about five feet above the floor.
- Keep it clear of drafts, dead air spots, direct sunlight and heat sources.
Applies to: Thermostat installation with the furnace
Source: Goodman GMVC96 service and troubleshooting manual, p. 8. Written in our own words; check the manual for your exact model.
Valid equipment combinations
Furnace · 34.5 inch chassis gas furnaces (ACVC96, AMVC96, GCVC96, GMVC96)
The furnace can be paired with: a furnace alone; a 1-stage or 2-stage non-communicating A/C or heat pump; a communicating A/C or heat pump; or a communicating A/C or heat pump inverter. All combinations assume a non-communicating single stage thermostat and AHRI matched equipment.
Applies to: Furnace system matching
Source: Goodman GMVC96 service and troubleshooting manual, p. 5. Written in our own words; check the manual for your exact model.
Venting restrictions and vent system check
Furnace · ACVC96/AMVC96/GCVC96/GMVC96
This furnace cannot connect to Type B, BW or L vent or vent connector, and cannot enter any part of a factory-built or masonry chimney, except as a pathway for PVC. Never common-vent it with another appliance or a solid-fuel vent. Use only the no-hub connectors shipped with the unit. Before leaving, check the whole flue system inside and out for sealing, because leaks can cause carbon monoxide exposure.
- Confirm the vent is not Type B, BW or L and is not common-vented.
- Confirm the vent does not run through a chimney except as a PVC pathway.
- Use only the supplied no-hub connectors.
- Inspect the full flue system inside and out for leaks before startup.
Applies to: All vented installations
Source: Goodman GMVC96 service and troubleshooting manual, p. 11. Written in our own words; check the manual for your exact model.
Wiring replacement and grounding requirements
Furnace · ACVC96/AMVC96/GCVC96/GMVC96
Wiring and grounding notes from the wiring diagram page that apply when servicing the furnace.
- Use copper conductors only.
- If any original wire supplied with the furnace must be replaced, use wiring rated for the temperature shown on the diagram note (the number is cut off in the text, so check the unit's own wiring label).
- Use the manufacturer's specified replacement parts when servicing.
- Permanently ground the unit in accordance with the National Electrical Code and local codes.
- Disconnect all power before servicing or installing the unit, since multiple power sources may be present.
Applies to: ACVC96/AMVC96/GCVC96/GMVC96 furnaces
Source: Goodman GMVC96 service and troubleshooting manual, p. 64. Written in our own words; check the manual for your exact model.
Related
Same tips in your pocket
The HVACopedia app has these tips, every error code and the settings tables offline.
For licensed technicians. Installer menus, test modes and access codes change settings that affect safety; only use them if you are trained on the appliance and understand the result. Gas, electrical and refrigerant work must be done by a qualified, licensed person, and the manufacturer’s manual for the exact model and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.