Goodman · Furnace troubleshooting

Blower motor does not have enough information, fails to start 40 consecutive times

ACVC96AMVC96GCVC96GMVC96

What is going on

The blower motor failed to start 40 times in a row, and the control says it lacks the information to run it properly. That can mean a data problem in the control module or a rotor that is locked up. Shut off power and confirm the circuit is dead before opening up the blower compartment.

Likely causes

  • Error with the integrated control module, such as missing or wrong shared data
  • Motor has a locked rotor condition

Check in this order

  1. Turn power off before repair and confirm it with a meter.
  2. Check the integrated control module and verify it holds the correct shared data set.
  3. Check for a locked rotor condition by turning the wheel by hand, and correct it.
  4. Use the memory card for the specific model if data needs to be reloaded.
  5. Replace the motor with the correct replacement part if needed.
  6. Restore power and confirm the blower starts normally.

Applies to: 34.5 in chassis gas furnaces

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Goodman GMVC96 Service and Troubleshooting, p. 63. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.