Goodman · Furnace troubleshooting

Upflow horizontal, right side down - drain setup

34.5 in Chassis ACVC96/AMVC96/GCVC96/GMVC96

What is going on

Drain trap and hose relocation for an upflow furnace laid on its right side. Needs at least 5.5 in clearance under the trap.

Check in this order

  1. Keep at least 5.5 in clearance beneath the drain trap.
  2. Remove the clamps from both drain hose ends.
  3. Remove the two trap screws from the blower deck, then remove the trap and both hoses.
  4. Move the two plugs from the right cabinet side to the blower deck.
  5. Drain the vent elbow cut 1 in from the 45 degree bend of hose #2 and discard the bend. Feed hose #2 through the top cabinet drain hole and clamp it to the elbow barb with a red clamp.
  6. Drain the collector box feed the non-grommet end of hose #11 through the bottom cabinet drain hole and clamp it to the collector box with a silver clamp.
  7. Clamp hoses to the trap with silver clamps. The trap outlet faces the furnace front. Secure the trap with the two removed screws through the large holes in the top tabs.
  8. Connect the field drain to the trap outlet per the field drain section.

Applies to: Upflow horizontal, right side down

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Goodman GMVC96 service manual, p. 21. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.