Goodman · Furnace troubleshooting
Upflow horizontal, left side down - drain setup
What is going on
Drain trap and hose relocation for an upflow furnace laid on its left side. Needs at least 5.5 in clearance under the trap. Hose cut lengths depend on cabinet width.
Check in this order
- Keep at least 5.5 in clearance beneath the drain trap.
- Remove the clamps from the two trap drain tubes.
- Remove the two trap screws from the blower deck, then remove the trap and hoses.
- Move the two plugs from the left cabinet side to the blower deck.
- Drain the vent elbow on hose #6, measured from the non-grommet end, cut off 1.5 in for a D width, 5 in for a C width, or 8.5 in for a B width.
- Fit hose #6 to the vent-drain elbow side port with a silver clamp. Move the rubber plug to the unused elbow drip port to seal it; a blunt tool such as a 3/16 in Allen wrench in the plug center helps it seat.
- Cut hose #5 3 in from the non-grommet end and discard that section. Feed the cut end through the lower cabinet drain hole.
- Join hose #6 and hose #5 with a 100 degree elbow and two red clamps.
- Drain the collector box move the cap from the left collector port (bottom) to the right (top) port. Feed the non-grommet end of hose #11 through the upper cabinet drain hole and clamp it to the collector box with a silver clamp.
- Clamp hoses to the trap with silver clamps. The trap outlet faces the furnace front. Secure the trap with the two removed screws through the large holes in the top tabs.
- Connect the field drain to the trap outlet per the field drain section.
Applies to: Upflow horizontal, left side down
More furnace guides
- Airflow lower than demanded, furnace runs on low stage when high stage is expected
- Alternate combustion air opening (upflow or horizontal)
- Alternate vent/flue location (upflow or horizontal left)
- Annual inspection checklist
- Auxiliary limit control (location and purpose)
- Auxiliary limit switch open (blower compartment)
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Goodman GMVC96 service manual, p. 22. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.