Test the ECM motor with the UltraCheck-EZ diagnostic tool

34.5 in. chassis ACVC96/AMVC96/GCVC96/GMVC96

What is going on

The UltraCheck-EZ (part UTT-01) is the preferred tool to diagnose the ECM motor. Use the LED and button status to decide the next step.

Check in this order

  1. Disconnect power to the furnace.
  2. Disconnect the 4-circuit control harness from the motor.
  3. Plug the 4-circuit connector from the tool into the motor control connector.
  4. Connect one alligator clip to a ground source and the other to a 24VAC source. The clips are not polarized.
  5. Only connect the tool to 24VAC. Other sources can blow the non-replaceable fuse and damage the tool.
  6. Turn on furnace power.
  7. Press the orange power button to send a run signal. Allow up to 5 seconds for the motor to start.
  8. If the orange button does not light, check for an open fuse or a bad 24VAC connection.
  9. Use the indication table to decide the next step.
  10. Press the orange button to turn the motor off, disconnect power, remove the tool, and reconnect the 4-wire harness.

Applies to: ECM blower motors on ACVC96/AMVC96/GCVC96/GMVC96

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Goodman GMVC96 service and troubleshooting manual, p. 44-45. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.