Goodman · Furnace troubleshooting
Temperature rise out of range - Goodman *MVC95/*CVC9
What is going on
Supply air too hot or too cold compared to the rating plate rise range.
Likely causes
- Heating blower tap set too low or too high
- Dirty filter or restricted ducts
- Wrong gas input
Check in this order
- Run the burners about 10 minutes with all registers open and dampers in their final position.
- Put thermometers in the supply and return ducts close to the furnace, out of sight of the heat exchanger.
- Rise = supply temp minus return temp. It must be inside the range on the rating plate.
- Too high raise the heating blower tap (S4 switches 7-8). Too low: lower it. Use the display airflow number to confirm.
- Check gas input clock the meter (natural gas) and compare to the rating plate. Final manifold pressure must stay within 0.3 in. w.c. of spec.
Applies to: GMVC95/AMVC95 upflow and *CVC9 counterflow two-stage furnaces
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Goodman *CVC9/95 & *MVC95 Installation Instructions IO-341D (08/2010), Temperature Rise p.39; Gas Input Rate p.39; Circulator Blower Speeds p.40-42. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.