Goodman · Furnace troubleshooting
Rollout switch open
What is going on
The rollout switch has opened and the furnace will not run. A rollout switch trips when flame or hot gas spills out of the burner compartment, so treat it as a real warning and never as a nuisance trip. Switch the power off before you open the furnace, and do not bypass the switch to get heat.
Likely causes
- Gas pressure too high, which pushes the flame out of the burner area
- Burners misaligned
- Restricted heat exchanger or venting, causing combustion gases to spill out
Check in this order
- Turn power off before service.
- Look for scorching, soot or melted wire insulation around the burner compartment.
- Check and correct gas pressure. This is licensed gas technician work.
- Check and correct burner alignment.
- Check and correct restrictions in the heat exchanger or venting.
- Only after the cause is fixed, reset or replace the switch, then watch a full cycle. Check for carbon monoxide at the vent and in the room.
Applies to: 34.5 in chassis gas furnaces
More furnace guides
- Airflow lower than demanded, furnace runs on low stage when high stage is expected
- Alternate combustion air opening (upflow or horizontal)
- Alternate vent/flue location (upflow or horizontal left)
- Annual inspection checklist
- Auxiliary limit control (location and purpose)
- Auxiliary limit switch open (blower compartment)
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Goodman GMVC96 Service and Troubleshooting, p. 62. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.