Goodman · Furnace troubleshooting

Rollout switch open

ACVC96AMVC96GCVC96GMVC96

What is going on

The rollout switch has opened and the furnace will not run. A rollout switch trips when flame or hot gas spills out of the burner compartment, so treat it as a real warning and never as a nuisance trip. Switch the power off before you open the furnace, and do not bypass the switch to get heat.

Likely causes

  • Gas pressure too high, which pushes the flame out of the burner area
  • Burners misaligned
  • Restricted heat exchanger or venting, causing combustion gases to spill out

Check in this order

  1. Turn power off before service.
  2. Look for scorching, soot or melted wire insulation around the burner compartment.
  3. Check and correct gas pressure. This is licensed gas technician work.
  4. Check and correct burner alignment.
  5. Check and correct restrictions in the heat exchanger or venting.
  6. Only after the cause is fixed, reset or replace the switch, then watch a full cycle. Check for carbon monoxide at the vent and in the room.

Applies to: 34.5 in chassis gas furnaces

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Goodman GMVC96 Service and Troubleshooting, p. 62. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.