Goodman · Furnace troubleshooting

Reversed line polarity

ACVC96AMVC96GCVC96GMVC96

What is going on

A polarity error means hot and neutral are swapped at the furnace, or the ground isn't good. The board checks it before it'll run, so it stays locked out until it's right. You see it a lot on new installs or after someone changed a plug-in or a receptacle.

Likely causes

  • 115 V AC polarity reversed
  • Poor unit ground
  • Wiring mistake at the disconnect or junction box

Check in this order

  1. Turn power off before service.
  2. Review the wiring diagram and correct the polarity.
  3. Verify the ground and correct if needed.
  4. Check the wiring at the disconnect and junction box and fix anything that's swapped.
  5. Restore power and confirm the error clears on the next call for heat.

Applies to: 34.5 in chassis gas furnaces

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Goodman GMVC96 Service and Troubleshooting, p. 61. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.