Lennox · Furnace troubleshooting
Poor ignition or loud combustion resonance - Lennox SL280UHNV
What is going on
SL280UHNV (ultra-low NOx air/gas burner) has trouble lighting or lights with a loud resonance. Hard ignition means too much combustion air (air orifice too large); resonance means too little air.
Likely causes
- Wrong or loose air orifice
- Plugged air inlet screen
- Vent/air intake restriction
- Kinked, loose or plugged signal hoses to gas valve
- Gas valve out of range
- Low supply voltage or gas pressure (-05 models)
Check in this order
- -05 and later confirm incoming voltage is 108-132 V and gas supply pressure is 5-14 in. w.c.; fix power or gas supply first.
- On -01 to -04 (not -040), make sure the inducer was slowed to 4300 RPM. If it wasn't, call your Lennox service rep.
- Check the air orifice (inside the gray coupling between the clamps): correct size per the orifice table, fully seated against the elbow, and air inlet screen clear.
- Check manifold pressure (-01 to -04 Table 18/19; -05 Table 23 0.0-0.10 in. w.c.). The gas valve is not adjustable - if manifold is out of range, replace the gas valve.
- If manifold is OK, check signal / system operating pressure (-05 Table 24). In range and still a problem: replace the air orifice; out of range: check vent/intake restriction, inlet screen and signal hoses.
- If pressure still wrong after fixing restrictions, replace the gas valve.
- Ignition problem after all checks fit the 'difficulty igniting' (smaller) air orifice. -05 resonance: install Low Profile Combustion Air Intake Kit 25B23 (-01 to -04: fit the 'resonance' larger orifice).
Applies to: Lennox SL280UHNV 80% communicating furnaces: SL280UH060NV36A, SL280UH080NV48B, SL280UH080NV60C, SL280UH100NV60C
More furnace guides
- AM radio static during ignition
- Blower motor does not run - Lennox SL280UHV ECM checks
- Burners light, then the furnace shuts down early
- Display shows two horizontal bars (soft disable) - Lennox SL297NV
- EL296UHV: normal gas heat sequence (what should happen after a call for heat)
- EL296UHV: what the display and the diagnostic button are telling you
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Lennox SL280UHNV Unit Information Corp 1601-L8 (rev 04/2024), Figure 22 p.37 and Figure 26 p.41; Air Orifice Replacement Tables 20/25 p.36, 39. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.