Lennox · Furnace troubleshooting

Blower motor does not run - Lennox SL280UHV ECM checks

What is going on

The variable-speed blower on a Lennox SL280UHV or SL280UHNV is an ECM, which means it is a motor with its own control module, and it will not run unless that module is happy. Before you pull the motor, look at the control display for a code. If there is no helpful code, the winding checks from the SL280UHNV service manual tell you whether the motor itself is damaged. Disconnect the power before testing, because you will be unplugging harnesses. A good meter and the right scale matter here.

Likely causes

  • Damaged motor windings
  • Motor or control module failure
  • Harness or connector problem
  • Control problem at the furnace board

Check in this order

  1. Warning: disconnect power before testing
  2. Check the control display for E201, E202, E292 or E295 and follow that code
  3. Test A measure resistance from each of the three motor leads (3-pin plug) to the unpainted end shield, below 100k ohms means replace the motor and control module, above 100k go to Test B
  4. Use an ohmmeter on the highest scale (100k or more) if it is not auto-ranging
  5. Test B measure lead-to-lead resistance on the 3-pin plug, each pair must be under 20 ohms and all pairs equal, over 20 ohms means replace the motor and control module
  6. If both tests pass, check the harness and furnace control instead
  7. Follow the manual for replacing the motor and module together

Applies to: Lennox SL280UHV (SL280UH070V36A, 090V36B, 090V48B, 090V60C, 110V60C, 135V60D) and SL280UHNV (SL280UH060NV36A, 080NV48B, 080NV60C, 100NV60C) 80% two-stage variable-speed communicating furnaces

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Lennox SL280UHNV Unit Information Corp 1601-L8 (rev 04/2024), Troubleshooting Motor Windings, Table 14 and Figures 11-12, p.28. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.