Furnace will not run (no heat) - Lennox EL195UHNE
What is going on
Quick checks from the manual when the EL195UHNE does not start on a call for heat.
Likely causes
- No heat call
- Access panel off (door interlock)
- Power off / fuse or breaker
- Dirty filter tripping the limit
- Gas off
- Ignition lockout (Watchguard)
Check in this order
- Confirm the thermostat is calling for heat (24 VAC on W).
- Make sure both access panels are on - the door interlock switch cuts line voltage.
- Check the main disconnect, fuses and breakers, and the 3 A circuit breaker CB8 in the control box.
- Check the filter; a plugged filter makes the limit shut the unit off (7 flashes).
- Confirm gas is on at the meter, the main manual valve and the internal valve.
- Read the red LED flash code and stored codes (press and release the recall button). If the unit is in lockout and locks out again, inspect for blockages (vent, intake, condensate drain).
Applies to: EL195UHNE
More furnace guides
- AM radio static during ignition
- Blower motor does not run - Lennox SL280UHV ECM checks
- Burners light, then the furnace shuts down early
- Display shows two horizontal bars (soft disable) - Lennox SL297NV
- EL296UHV: normal gas heat sequence (what should happen after a call for heat)
- EL296UHV: what the display and the diagnostic button are telling you
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Lennox EL195UHNE Unit Information Corp 1801-L1 (rev 04/2024), III Start-Up, Failure To Operate, p.39. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.