Lennox · Furnace troubleshooting
Display shows two horizontal bars (soft disable) - Lennox SL297NV
What is going on
Two horizontal bars on the 7-segment display. Lennox SL297UHNV in an iComfort system. The thermostat found a device on the RSBus it doesn't recognize. It puts that device in soft disable until it is set up. Usually wiring or a missing setup step.
Likely causes
- Miswired RSBus between thermostat, damper control, indoor and outdoor units
- Device not set up in the thermostat
- New or replaced control not yet recognized
- Loose connection at an RSBus terminal
Check in this order
- Confirm wiring between all devices (thermostat, damper control module, indoor and outdoor units), checking for loose, swapped or broken conductors
- Cycle power to the control that shows the bars, power off at the disconnect first, then back on
- Run the room thermostat through setup
- In the thermostat go to setup / system devices / thermostat / edit and press reset
- If needed repeat and press resetAll
- After setup, confirm the display clears and the system devices all show up in the thermostat
Applies to: SL297UHNV in iComfort communicating systems
More furnace guides
- AM radio static during ignition
- Blower motor does not run - Lennox SL280UHV ECM checks
- Burners light, then the furnace shuts down early
- EL296UHV: normal gas heat sequence (what should happen after a call for heat)
- EL296UHV: what the display and the diagnostic button are telling you
- Furnace will not run (no heat) - Lennox EL195UHNE
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Lennox SL297UHNV Installation Instructions 507760-02 (02/2018), Integrated Control Diagnostic Modes, Soft Disable, p.54. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.