EL296UHV: what the display and the diagnostic button are telling you

What is going on

The furnace control has a seven-segment display and one push button. Normal operation, stored errors, flame current and the unit size are all read from it.

Check in this order

  1. Watch the display with the furnace idle a blinking dot means idle. C, H, d, h or dF followed by a number means a call is running.
  2. To read stored errors, hold the button until E shows and release. The last 10 codes scroll. Choose c and press again while it flashes to clear them.
  3. To check the flame sensor, hold until F shows and release. Normal is 2.6 microamps or more. 2.5 or less is low. Drop out is 1.1.
  4. Hold until three bars show to go back to normal. Menus time out on their own.

Applies to: EL296UHV(X) series

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Lennox EL296UHV(X) Unit Information, Corp 1125-L5 (rev. 03/2022), Tables 4-5 (diagnostic modes and LED codes), printed p.32-33. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.