Goodman · Furnace troubleshooting

Open fuse, no furnace operation

ACVC96AMVC96GCVC96GMVC96

What is going on

The furnace is dead or won't run, and the 3-amp control fuse on the board has blown. That fuse protects the 24 V side, so a blown one almost always means something is shorting in the low voltage wiring. Just swapping the fuse usually gets you another blown fuse a minute later.

Likely causes

  • Open fuse
  • Short in low voltage wiring, such as a pinched or chafed thermostat wire, a staple through the cable, or a bad accessory like a humidifier or relay

Check in this order

  1. Turn power off before repair.
  2. Locate and correct the short in the low voltage wiring.
  3. Look along the thermostat wire runs and at the cabinet edges where the wire passes through. Disconnect any add-ons one at a time to see if one is the cause.
  4. Replace the fuse with a 3-amp automotive type fuse.
  5. Restore power and watch the furnace through a full cycle.

Applies to: 34.5 in chassis gas furnaces

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Goodman GMVC96 Service and Troubleshooting, p. 61. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.