Goodman · Furnace troubleshooting

Non-direct vent (single pipe) termination

ACVC96/AMVC96/GCVC96/GMVC96

What is going on

Non-direct vent, single pipe, means the furnace pulls its combustion air from the room and only the flue pipe goes outside. It can exit horizontally through a side wall, vertically through the roof, or run up an unused chimney with at least 12 in. above the chimney top. The usual headaches are snow burying the termination and weather leaking in around the penetration.

Likely causes

  • Termination too low and buried by snow
  • Unsealed roof or chimney penetration leaking weather in
  • Elbow or tee pointing up on a wall exit, letting rain in
  • Gap around the pipe in the chimney left open

Check in this order

  1. Keep the termination at least 12 in. above the highest anticipated snow level.
  2. For a vertical roof exit, seal the penetration with flashing such as used for plastic plumbing vents.
  3. For a horizontal wall exit, use the termination shown in the figure and point any elbow or tee downward.
  4. For a chimney run, seal the gap between pipe and chimney with weather-tight, corrosion-resistant flashing.
  5. Check that the room supplies adequate combustion air for a non-direct vent system.
  6. After install, inspect the termination from outside during a heat call.

Applies to: Non-direct vent installations

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Goodman GMVC96 service and troubleshooting manual, p. 15-16. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.