Measure and adjust manifold gas pressure (36J54 valve)
What is going on
Manifold pressure is measured with burners operating. Only small variations should be made with the valve pressure regulator. Do not derate the furnace by setting manifold pressure below the rating plate value.
Likely causes
- Manifold pressure outside the table range
- Regulator out of adjustment
Check in this order
- Shut off gas at the manual shutoff, then shut off all electrical power.
- On the White-Rodgers 36J54, back the outlet pressure test screw out one turn counterclockwise (no more than one turn).
- Attach a hose and manometer to the outlet pressure tap.
- Turn on gas and power, then run the high fire or low fire test.
- Adjust the high fire or low fire regulator so manifold pressure matches the table.
- Turn off gas, remove the manometer and reinstall the test screw and plug.
- Turn on gas, check for leaks and verify operation.
Applies to: 36J54 gas valve, natural and propane
More furnace guides
- Airflow lower than demanded, furnace runs on low stage when high stage is expected
- Alternate combustion air opening (upflow or horizontal)
- Alternate vent/flue location (upflow or horizontal left)
- Annual inspection checklist
- Auxiliary limit control (location and purpose)
- Auxiliary limit switch open (blower compartment)
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Goodman GMVC96 service manual, p. 52-53. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.