Goodman · Furnace troubleshooting

Low stage pressure switch contacts not closed

ACVC96AMVC96GCVC96GMVC96

What is going on

The control is looking for the low stage pressure switch to close and it isn't seeing it. That switch tells the control the inducer is pulling a draft, so without it the furnace won't go on to light. Usually it's the switch, its hose, or something in the wiring.

Likely causes

  • Low stage pressure switch contacts sticking
  • A short in the pressure switch circuit wiring
  • A cracked, pinched or plugged pressure switch hose

Check in this order

  1. Inspect the pressure switch hose and repair or replace it if it is cracked, kinked or has water in it.
  2. Look over the pressure switch wiring with the power off for rubbed insulation or shorts.
  3. Repair the short in the wiring if you find one.
  4. Watch the switch during an inducer start and see whether it closes.
  5. Replace the low stage pressure switch if the contacts stick.
  6. Do not jumper the switch. It is a safety device.

Applies to: 34.5 in chassis gas furnaces

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Goodman GMVC96 Service and Troubleshooting, p. 61. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.