Goodman · Furnace troubleshooting

Low flame signal, furnace runs normally

ACVC96AMVC96GCVC96GMVC96

What is going on

The furnace is still lighting and heating, but the flame sense micro amp signal is lower than it should be. A low signal can drop out and cause nuisance lockouts later, so catch it now. Shut the power off and let the burner area cool before reaching in.

Likely causes

  • Flame sensor coated or oxidized
  • Flame sensor not positioned correctly in the burner flame
  • Lazy burner flame from improper gas pressure or combustion air

Check in this order

  1. Turn power off before any repair and let things cool.
  2. Clean the flame sensor with steel wool if it is coated or oxidized.
  3. Inspect the sensor for proper alignment in the burner flame.
  4. Check inlet air piping for blockage, proper length, elbows and termination.
  5. Compare the current gas pressure to the rating plate and adjust as needed. Gas pressure adjustment is for a licensed gas technician.
  6. Restore power, run a cycle and recheck the flame signal.

Applies to: 34.5 in chassis gas furnaces

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Goodman GMVC96 Service and Troubleshooting, p. 61. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.