Goodman · Furnace troubleshooting

Loss of flame after establishment

ACVC96AMVC96GCVC96GMVC96

What is going on

Burners light, then drop out. Flame is established and then it is gone. Often a few seconds later it tries again. Look at what changes right after light off: gas, draft, or flame sensing. Start with the easy stuff.

Likely causes

  • Interrupted gas supply
  • Lazy burner flames from improper gas pressure or restriction in flue and/or combustion air piping
  • Front cover pressure switch opening
  • Improper induced draft blower performance
  • Coated or oxidized flame sensor
  • Weak or poorly aligned igniter

Check in this order

  1. Locate and correct the gas interruption. Gas work is for a licensed gas tech
  2. Check front cover pressure switch operation (hose, wiring, contacts). Correct if needed
  3. Replace or realign the igniter
  4. Check the flame sense signal. Sand the sensor if coated or oxidized
  5. Check flue piping for blockage, proper length, elbows and termination
  6. Verify proper induced draft blower performance
  7. Watch the flame on a full trial. Note whether it goes out before or after the inducer changes speed

Applies to: 34.5 in chassis gas furnaces

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Goodman GMVC96 Service and Troubleshooting, p. 60. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.