Loss of communication with circulator blower motor

ACVC96AMVC96GCVC96GMVC96

What is going on

The integrated control module and the circulator motor have stopped talking to each other, and the furnace won't run. What I usually find is a plug that's backed out or a loose control lead, so start there before you condemn the motor. Motor and board both fail occasionally, but wiring comes first.

Likely causes

  • Loose wiring at the circulator motor control leads
  • Failed circulator blower motor
  • Failed integrated control module

Check in this order

  1. Turn power off before repair.
  2. Reseat and tighten the motor control lead connections and look for pins that are pushed back or corroded.
  3. Tighten or correct the wiring connection wherever you find a fault.
  4. Check the circulator blower motor and replace it if needed.
  5. Check the integrated control module and replace it if needed, once wiring and motor are cleared.
  6. Restore power and watch for communication on a call for heat.

Applies to: 34.5 in chassis gas furnaces

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Goodman GMVC96 Service and Troubleshooting, p. 63. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.