Lennox · Furnace troubleshooting
Inducer runs but the ignitor does not warm up
What is going on
The inducer comes on with a heat call but the ignitor never glows and no flame follows. The control flashes the pressure switch code about 2.5 minutes after the call.
Likely causes
- Prove switch tubing routed wrong, blocked, leaking or holding condensate
- Low differential pressure from a blocked intake or exhaust or wrong vent sizing
- Wrong or out-of-calibration prove switch
- Loose or wrong wiring at the prove switch
- Prove switch failed
Check in this order
- Turn off power at the disconnect before touching wiring or components.
- Check the tubing for correct routing, obstructions, leaks and condensate.
- Check the differential pressure across the switch against the set point on the switch.
- Check intake and exhaust for blockage and check vent size and length.
- Check the right switch is installed and its wiring is tight. Replace the switch if all else checks out.
Applies to: G43UF-24B-045 through G43UF-60D-135 (SureLight boards 32M88, 78M47, 100973-01)
More furnace guides
- AM radio static during ignition
- Blower motor does not run - Lennox SL280UHV ECM checks
- Burners light, then the furnace shuts down early
- Display shows two horizontal bars (soft disable) - Lennox SL297NV
- EL296UHV: normal gas heat sequence (what should happen after a call for heat)
- EL296UHV: what the display and the diagnostic button are telling you
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Lennox G43UF Unit Information Corp. 0416-L4, Troubleshooting Chart Problem 3 p.52. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.