Lennox · Furnace troubleshooting
Indoor blower does not run - Lennox EL195UHNE
What is going on
Constant-torque ECM blower motor check on the EL195UHNE. The motor needs 120 VAC on J48 and 24 VAC (12-33 VAC) on one speed tap of J49.
Likely causes
- No 120 V at the motor
- No 24 V on the active speed tap
- Harness fault
- Failed motor or motor module
Check in this order
- Warning: Shut off power before unplugging J48/J49.
- Test 1 power on, check 120 VAC across L and N (or 7A and 9A) of J48; if missing check L1 to Neutrals on the control.
- Test 2 thermostat on continuous fan, check 24 VAC between C of J48 (or pin 6A on 6-pin plugs) and the fan tap on J49; if missing check 24 COM to the active tap on the control.
- Both voltages present and motor not running right: replace the motor, or the module only on motors with 4-pin power and 5-pin signal plugs.
- Before fitting a new module each motor pin to end plate more than 100k ohms, three windings equal within about 1 ohm, and the wheel spins freely.
- Torque module bolts to 22 in-lb; connectors face down for a drip loop.
Applies to: EL195UHNE
More furnace guides
- AM radio static during ignition
- Blower motor does not run - Lennox SL280UHV ECM checks
- Burners light, then the furnace shuts down early
- Display shows two horizontal bars (soft disable) - Lennox SL297NV
- EL296UHV: normal gas heat sequence (what should happen after a call for heat)
- EL296UHV: what the display and the diagnostic button are telling you
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Lennox EL195UHNE Unit Information Corp 1801-L1 (rev 04/2024), C - Blower Compartment, Figures 10-17, p.15-17. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.