Goodman · Furnace troubleshooting

Igniter fault or improper grounding

ACVC96AMVC96GCVC96GMVC96

What is going on

Furnace is locked out on an igniter circuit error. Control sees a bad igniter circuit or a bad ground. Check wiring and ground first, then igniter, then board. Power off before you touch it.

Likely causes

  • Problem with igniter circuit wiring
  • Improperly connected igniter
  • Shorted igniter
  • Poor unit ground
  • Igniter relay fault on the integrated control module

Check in this order

  1. Turn power off before repair
  2. Check and correct wiring from the control module to the igniter. Look at the plug for burnt pins
  3. Replace a shorted igniter with the correct part
  4. Check and correct the unit ground wiring. A loose ground gives odd igniter faults
  5. Check igniter output from the control and replace if needed
  6. Replace the control module with the correct part if the igniter relay has failed
  7. Handle the igniter by the base, never the element

Applies to: 34.5 in chassis gas furnaces

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Goodman GMVC96 Service and Troubleshooting, p. 61. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.