Goodman · Furnace troubleshooting

Horizontal installation: suspension, leveling and drain

ACVC96/AMVC96/GCVC96/GMVC96

What is going on

Horizontal furnaces need proper support, a level end-to-end set-up with a slight forward tilt, and a trap drop for condensate. Crawl space units must be suspended from floor joists or set on a concrete pad.

Likely causes

  • Furnace sagging or sloping backward, so condensate does not drain
  • Drain trap too close to the furnace bottom

Check in this order

  1. If suspending from rafters or joists, use 3/8 in. threaded rod and 2 x 2 x 1/8 in. angle iron as shown in the figure.
  2. Crawl space suspend from the floor joist or support on a concrete pad. Never set it on the ground or let it sit in water.
  3. Level the furnace from end to end with a slight forward tilt so the access doors sit about 1/2 to 3/4 in. lower than the back panel.
  4. Mount the condensate trap to the side panel with at least 5 1/2 in. of clearance below the furnace.
  5. Slope the drain line down from the trap to the drain point.
  6. Protect the trap and drain line from freezing if they are exposed to near-freezing temperatures.

Applies to: Horizontal installations

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Goodman GMVC96 service and troubleshooting manual, pp. 9-10. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.