Lennox · Furnace troubleshooting
Furnace will not run - Lennox SL280UHV checklist
What is going on
SL280UHV / SL280UHNV furnace does not start on a heat call; basic checks from the installation manual before deeper diagnosis.
Likely causes
- No thermostat call
- Panels off (door interlock open)
- Power off, blown fuse or tripped breaker (incl. 3 A 24 V breaker)
- Gas off
- Dirty filter tripping limit
- Lockout
- Pressure switch open (blocked flue)
- Flame rollout switch tripped
Check in this order
- Confirm the thermostat is calling for heat.
- Make sure the access panels are on (door interlock switch).
- Check the main disconnect, fuses/breakers, and the 24 V circuit breaker on the control box (3 A, push to reset).
- Make sure gas is on at the meter, the main manual shut-off and the internal gas valve switch.
- Check the filter - a dirty filter makes the limit shut the unit off.
- Check the 7-segment display for an error code (hold the button for 'E' to recall the last 10 codes). Watchguard lockout resets after one hour.
- Check the pressure switches and flue/vent outlet for blockage.
- Warning: If a flame rollout switch has tripped, find the cause (combustion air, blocked vent) before resetting it.
Applies to: Lennox SL280UHV (SL280UH070V36A, 090V36B, 090V48B, 090V60C, 110V60C, 135V60D) and SL280UHNV (SL280UH060NV36A, 080NV48B, 080NV60C, 100NV60C) 80% two-stage variable-speed communicating furnaces
More furnace guides
- AM radio static during ignition
- Blower motor does not run - Lennox SL280UHV ECM checks
- Burners light, then the furnace shuts down early
- Display shows two horizontal bars (soft disable) - Lennox SL297NV
- EL296UHV: normal gas heat sequence (what should happen after a call for heat)
- EL296UHV: what the display and the diagnostic button are telling you
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Lennox SL280UHV Installation Instructions 508245-01 (04/2024), Failure To Operate, p.44; Lennox SL280UHNV Unit Information Corp 1601-L8 (rev 04/2024), Circuit Breaker CB8, p.11. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.